Insulation resistance is measured with a DC voltage, and the choice of that voltage is one of the few places where the standard leaves the engineer to think. The rule is simple: the test voltage should be close to the working voltage, and never so high that it damages what it is measuring.
A megohmmeter set to 1000 V on a 230 V product with a thin film insulation is not a stricter test, it is a different one, and it can leave a permanent partial discharge path behind.
The usual mapping
| Circuit working voltage | Test voltage | Typical minimum reading |
| Below 50 V (SELV) | 250 V DC | 1 MΩ to 2 MΩ |
| 50 V to 250 V | 500 V DC | 2 MΩ to 5 MΩ |
| 250 V to 500 V | 500 V DC to 1000 V DC | 5 MΩ |
| Above 500 V | 1000 V DC | 5 MΩ to 10 MΩ |
| After damp heat | Same voltage, lower limit | 1 MΩ often accepted |
| Double insulation, class II | 500 V DC | 2 MΩ to 7 MΩ |
The minimum reading is not a measure of quality; it is a threshold for a wet, dirty, real-world insulation. A clean dry sample reads hundreds of megohms, and that number says very little.
Reading that is stable enough to record
- Wait for the value to settle. Capacitance charges first; the reading climbs for ten to sixty seconds.
- Note the polarity. Some films read differently in one direction, and a reversed reading is not comparable.
- Guard the surface. Surface leakage across a dirty moulding can dominate a 5 MΩ reading.
- Test at the same temperature. Insulation resistance roughly halves for every 10 K rise on many materials.
Why the number is a screening value
Insulation resistance catches moisture, contamination and gross damage. It does not catch a pinhole that only breaks down at 3 kV, which is what the dielectric test is for. The two tests answer different questions and neither replaces the other.
In production, the resistance test is the one you can run on every unit in a few seconds; the dielectric test runs on a sample. Instruments that log both, with the voltage and the settling time, make the comparison between shift and shift possible. Our insulation resistance testers cover 250 V to 1000 V ranges, and the technical notes give the settle times for each range.
Standards referenced: IEC 60335-1 clause 16.3, IEC 61010-1 clause 6.8.3, IEC 60601-1 clause 8.8.3 for the medical equivalent.
Production readings that mean something
On a production line the value is a screen, not a measurement: a 2 s reading at 500 V separates a dry unit at 200 MΩ from a wet one at 3 MΩ reliably, and that is all it needs to do. Save the 60 s stabilised reading for the type test and the dispute.
Keep the probe tips clean and the test jig dry; a fingerprint on a moulding can halve the reading at 500 V.